Kitchen exhaust duct calculator — grease duct size and velocity

Grease duct is sized to a velocity window, not a friction rate. Enter the hood exhaust airflow, pick the velocity your authority or hood listing asks for, and get the duct size that lands inside the window — round or rectangular — with the actual velocity, the friction loss of the run and a check against the code minimum.

The size closest to this velocity, inside the window, is chosen.

Grease duct size

18 in ø

Velocity 1,698 fpm (8.62 m/s) · required window 1,500–2,500 fpm

Kitchen exhaust duct results
Actual velocity in the duct1,698 fpm (8.62 m/s)
Exact area at the design velocity0.1548 m² · 240 in²
Area of the selected size0.1642 m² · 254 in²
Aspect ration/a — round
Friction rate (welded steel)1.48 Pa/m · 0.1808 in.wg/100 ft
Straight duct loss over the run18 Pa · 0.07 in.wg
Velocity pressure42 Pa · 0.17 in.wg
Duct weight at 1.37 mm carbon steel15.4 kg/m · 10.4 lb/ft

In the windowThe selected size runs at 1,698 fpm (8.62 m/s), inside the required range. Velocity is checked on the real duct area — never on the equivalent round diameter.

The straight-duct loss excludes the hood, filters, elbows and the fan connection — add those from the hood manufacturer and the fitting loss calculator. Construction, clearances, access panels and fire-rated enclosures follow NFPA 96 or the local mechanical code.

Sized to a velocity window, not a friction rate

Every other duct on a project is sized to keep pressure loss and noise down. Grease duct is different: it carries hot, grease-laden vapour that condenses on cold surfaces, and a duct coated in grease is a fire load running through the building. The velocity requirement exists to keep that vapour moving and to keep the duct small enough to clean.

For most of the twentieth century the rule was a flat 1500 fpm minimum. Nobody is entirely sure where the number came from — one widely repeated explanation is that it was carried over from an old requirement for coal furnace flues. Research on grease transport in the late 1990s led NFPA 96 to drop the minimum to 500 fpm (2.54 m/s) in 2002, and ASHRAE Standard 154 followed the same direction.

In practice both numbers are still in use. Many authorities, local amendments and hood test forms continue to require 1500 fpm minimum and 2500 fpm maximum for shop-built hoods, while listed hoods follow their listing. A grease duct is therefore sized to a window, and the first job is to find out which window applies.

How to use the kitchen exhaust duct calculator

  1. Enter the hood exhaust airflow. The total exhaust the hood is listed or designed for — from the hood schedule or the manufacturer selection, not an estimate from the cooking line.
  2. Choose the velocity requirement. Listed hoods follow the manufacturer listing. Shop-built hoods are commonly held to 1500–2500 fpm by the authority having jurisdiction. If only the NFPA 96 minimum applies, choose that — but check locally first.
  3. Set the design velocity. The tool picks the size closest to this figure while staying inside the window. Designing near the middle of the window leaves room for the airflow to drift on commissioning.
  4. Pick round or rectangular. For rectangular, fix the side the route allows and the tool solves the other. Round is easier to weld and clean and has the least surface for grease to collect on.
  5. Check the velocity and the run loss. Velocity is reported on the real duct area. Add the straight-run loss to the hood, filter and fitting losses before selecting the fan.

Velocity requirements in use

Grease duct velocity requirements
Basisfpmm/s
NFPA 96 minimum (since 2002)500 min2.54 min
Shop-built hood, common local requirement1500–25007.6–12.7
NFPA 96 before 2002 (historic)1500 min7.6 min
Listed hoodPer the manufacturer listing

Always confirm the edition of NFPA 96 or the mechanical code adopted by the authority having jurisdiction, and any local amendment, before fixing the duct size.

Formulas and a worked example

  • Required area: A = Q ÷ V
  • Round duct: D = √(4A ÷ π)
  • Velocity check: V = Q ÷ Aactual, on the real section area

A hood exhausting 3000 CFM, shop-built, designed to 1800 fpm inside a 1500–2500 fpm window. Required area = 3000 ÷ 1800 = 1.67 ft² (240 in²), an exact round diameter of 17.5 in. A 16 inch duct would run at 2149 fpm and an 18 inch at 1698 fpm — both inside the window, and the 18 inch is closer to the design velocity, so it is selected. Under the NFPA 96 minimum alone a much larger duct would be legal, but the 1500 fpm local requirement would rule out a 20 inch duct or anything larger.

Things to keep in mind

  • Velocity on the real area. Never check grease duct velocity on the circular equivalent diameter — it overstates the velocity of a rectangular duct.
  • Construction comes with the size. Continuous liquid-tight welds, cleanout openings at changes of direction, grease-draining slopes and the clearance to combustibles — 18 in for an unprotected duct under NFPA 96 — all follow from the code, not from this calculation.
  • Make-up air is half the system. Every cubic foot exhausted has to be replaced. An exhaust duct sized correctly but starved of make-up air will not deliver its design airflow.
  • The duct is only part of the loss. Hood, filters, elbows, the fan inlet and the discharge all add pressure. Total them before selecting the fan.
  • Hot air is lighter. The temperature you enter sets the density used for the friction and velocity pressure figures; exhaust from heavy cooking lines runs well above room temperature.

Frequently asked questions

What is the minimum velocity in a kitchen exhaust duct?

NFPA 96 sets a minimum of 500 fpm (2.54 m/s) through the grease duct. It was 1500 fpm for decades; the 2001 edition moved it to 1200, and an errata early in 2002 corrected it to 500 fpm following research on grease transport. Many authorities and hood test forms still apply 1500 fpm minimum and 2500 fpm maximum to shop-built hoods, so confirm which requirement is enforced where the job is.

Why do some inspectors still ask for 1500 fpm?

Because 1500 fpm was the requirement for most of the last century, and it remains written into older adopted code editions, local amendments and municipal hood test forms. It also has practical merit: a faster duct keeps grease droplets airborne and shrinks the duct. The 500 fpm figure is a minimum, not a recommendation to design that slowly.

How do I calculate kitchen exhaust duct size?

Divide the hood exhaust airflow by the design velocity to get the area, then pick a size. 3000 CFM at 1800 fpm needs 1.67 ft², or 240 square inches; an 18 inch round duct gives 254 square inches and runs at about 1700 fpm, inside a 1500–2500 fpm window.

Should I use equivalent diameter to check grease duct velocity?

No. Velocity is airflow divided by the real cross-sectional area of the duct. The circular equivalent diameter belongs to friction calculations, and its smaller area gives a higher velocity than the duct actually has — which can make an undersized-velocity rectangular duct look compliant when it is not.

What thickness of steel is required for grease duct?

NFPA 96 calls for carbon steel of at least 1.37 mm (0.054 in, No. 16 MSG) or stainless steel of at least 1.09 mm (0.043 in, No. 18 MSG), with liquid-tight continuous external welds. Factory-built listed grease duct systems follow their own listing. The weight shown by this tool assumes the 1.37 mm carbon steel minimum.

Does a bigger grease duct make the kitchen quieter?

It lowers the duct velocity and the fan pressure, but only as far as the velocity window allows. Drop below the minimum and the duct is non-compliant regardless of how quiet it is. Noise at the hood is mostly set by the filters and the hood design, not by the duct.

Last updated: 24 October 2026